Approvals & Certifications
Set Point Range - Increasing - psi
Set Point Range - Decreasing - psi
- Minimum: 0.95
- Maximum: 98.5
Set Point Range - Increasing - kPa
- Minimum: 6.895
- Maximum: 689.4757
Set Point Range - Decreasing- kPa
- Minimum: 6.55
- Maximum: 679.1336
Set Point Range - Increasing - bar
- Minimum: 0.069
- Maximum: 6.89
Set Point Range - Decreasing - bar
- Minimum: 0.065
- Maximum: 6.79
Set Point Range - Incr. - Inches H2O
Set Point Range - Decr. - Inches H2O
- Minimum: 1.5
- Maximum: 76.5
Set Point Range - Incr. - mbar
- Minimum: 12.4
- Maximum: 199.3
Set Point Range - Decr. - mbar
- Minimum: 3.74
- Maximum: 191
Deadband, Approx. - Inches H2O
Deadband, Approx. - mbar
- Minimum: 6.23
- Maximum: 68.9
System Pressure - Max.
- 35 psig : 2.41 bar : 1.676 kPa
- 75 psig : 5.17 bar : 3.59 kPa
- 200 psig : 13.79 bar : 9.58 kPa
Proof Pressure - Max.
- 50 psig : 3.45 bar : 2.4 kPa
- 100 psig : 6.89 bar : 4.8 kPa
- 250 psig : 17.2 bar : 1723.68 kPa
Process Connection Type & Size
Process Connection Material
Reset Function - Auto or Manual
Electrical Connection Size
- 3/4" NPT Female Conduit Connection
Electrical Termination Type
Electrical Contacts Material
Voltage Electrical Rating
- 0 - 250 VAC
- 251 - 480 VAC
- 0 - 125 VDC
- 126 - 250 VDC
System Pressure
- bar: 2.41 to 13.79
- kPa: 241.4 to 1,379
- psig: 35 to 200
Proof Pressure
- bar: 3.45 to 17.24
- kPa: 344.8 to 1,724
- psig: 50 to 250
Deadband, Approximate
- inH₂O: 2.5
- mbar: 6.23 to 68.9
- psi: 0.1 to 1
Electrical Rating
- Gold Contacts Option: 1 A Max.
- SPDT: 15 A at 125/250/480 Vac Res, 0.4 A at 125 Vdc, 0.2 A at 250 Vdc
Set Point Range - Increasing
- bar: 0.069 to 6.895
- inH₂O: 5 to 80
- kPa: 6.895 to 689.5
- mbar: 12.4 to 199.3
- psig: 1 to 100
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Set Point Range - Decreasing
- bar: 0.065 to 6.791
- inH₂O: 1.5 to 76.5
- kPa: 06.55 to 679.1
- mbar: 3.74 to 191
- psi: 00.95 to 98.5
Approvals & Certifications
- CE
- CRN - Canadian Registration Number
- CRN - Saskatchewan
- EMC
- LVD
- RoHS