Brand: Custom Control Sensors, LLCThe 605G Series is a weather resistant, general purpose gage pressure switch.
It is modelled after the 604 Series, designed specifically for high-ingress and corrosion-resistant applications.
It has a modified face-down side port electrical connection, preventing any liquids from seeping into the inner workings of the switch.
The 605G Series is easily mounted to bulkheads and ideal for extreme wet conditions, rated to NEMA 4X and IP66.
Features- Adjustable Set Point Range
- Increasing
- psig 1 - 1000
- kPa 6.89 - 6894.7
- bar 0.07 - 68.9
- Decreasing
- psig 0.3 - 935
- kPa 2.1 - 6446.5
- bar 0.02 - 64.5
- Increasing
- Deadband - Approximate: 0.7 - 65 psi, 4.9 - 448.1 kPa, 0.05 - 4.5 bar
- System Pressure - Maximum: 500 - 3000 psig, 3337.4 - 20,684.2 kPa, 34.5 - 207 bar
- Proof Pressure: 750 - 5000 psig, 5171.1 - 34,473.7 kPa, 51.7 - 345 bar
- Wetted Materials
- Pressure Port: 1/4" Female NPT Aluminum
- Diaphragm: Polyimide
- O-Ring: Buna N
- Relay: SPDT or DPDT
- CRN, CE Mark, General Purpose
Specifications
Area Classification
- Non-Hazardous Area
Approvals
- CE
- CCC
Adjustable or Pre-Set Set Point
- Field Adjustable
Set Point - PSI ▲
- Minimum: 1
- Maximum: 1000
Set Point - PSI ▼
- Minimum: 0.3
- Maximum: 935
Set Point - kPa ▲
- Minimum: 6.89
- Maximum: 6894.75
Set Point - kPa ▼
- Minimum: 2.068
- Maximum: 6446.59
Set Point - BAR ▲
- Minimum: 0.07
- Maximum: 68.9
Set Point - BAR ▼
- Minimum: 0.02
- Maximum: 64.5
Deadband - PSI Approx.
- Minimum: 0.7
- Maximum: 65
Deadband - BAR - approx.
- Minimum: 0.05
- Maximum: 4.5
Process Connection Type & Size
- 1/4"-18 NPT Female
- 1/2"-14 NPT Female - Welded Capsule, No O-Ring
Process Connection Material
- Aluminum
- Monel
- Hastelloy C-276
System Pressure - Max.
- 500 psig : 34.5 bar : 3447 kPa
Proof Pressure - Max.
- 750 psig : 51.7 bar : 5171 kPa
Diaphragm Material
- Polyimide
- Monel
- Hastelloy C-276
NACE
- NACE MR 0175 / ISO 15156
O-Ring
- Buna-N
- Ethylene Propylene
- Viton
- No O-Ring c/w Welded Capsule
Enclosure Rating
- IP 66
- NEMA 4
- NEMA 4X
- NEMA 13
Operating Temp. Range °C
- Minimum: -40
- Maximum: 86
Operating Temp. Range °F
- Minimum: -40
- Maximum: 186
Reset Function - Auto or Manual
- Auto
- Manual on Increasing Pressure
Electrical Connection Size
- 1/2" -14 NPT Female
Electrical Termination Type
- Terminal Strip
Electrical Contacts Form
- SPDT
- DPDT
- Double Break
Electrical Contacts Material
- Silver
- Gold
Voltage Electrical Rating
- 0 - 250 VAC
- 251 - 480 VAC
- 0 - 125 VDC
- 126 - 250 VDC
Ampere Rating
- 0.2 to 15 A
RoHS
Housing Material
- Aluminum
Gender
- Female
Manual Reset
- Manual Reset on Increasing Pressure
Proof Pressure
- bar: 51.7 to 345
- kPa: 5,171 to 34,473
- psig: 750 to 5,000
Enclosure, Body Material
- Aluminum
Environmental Protection
- IP 54
- IP 66
- NEMA 4
- NEMA 4X
- NEMA 13
Set Point Range - Increasing
- bar: 0.07 to 68.9
- kPa: 6.9 to 6,895
- psig: 1 to 1,000
Electrical Contacts
- Silver
- Gold
Set Point Range - Decreasing
- bar: 0.02 to 64.5
- kPa: 2.1 to 6,446
- psig: 0.3 to 935
Approvals & Certifications
- CE
- CRN - Canadian Registration Number
- CRN - Alberta
- CRN - British Columbia
- CRN - Saskatchewan
- EMC
- LVD
- PED
- RoHS
Switch Type
- SPDT
- DPDT
Diaphragm Material
- Polyimide
Standard Features
- Internal Case Ground
- Weatherproof
Electrical Connectors
- 1/2" NPT Male
Electrical Rating
- 1 A at 125 Vac, 50/60 Hz
- 15 A at 125/250/480 Vac Resistive, 0.4 A at 125 Vdc, 0.2 A at 250 Vdc
- 5 A at 125/250 Vac Resistive, 5 A at 28 Vdc, 0.5 A at 125 Vdc
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Adjustment Type
- Field Adjustable
Deadband, Approximate
- bar: 0.05 to 4.5
- kPa: 4.9 to 448.1
- psig: 0.7 to 65
System Pressure
- bar: 34.5 to 207
- kPa: 3,447 to 20,684
- psig: 500 to 3,000
O-Ring Material
- Buna-N
- Ethylene Propylene (EPR)
- Viton
Service
- Sweet - Oil & Gas
Process Connection
- 1/4" NPT Female
Area Classification
- Non-Hazardous Area
- Chemical Refining & Processing
- Fluid Management
- Heavy Vehicles
- Manufacturing Process
- Rail Car
- Power Generation
- Safety Systems
- Utilities, Water Treatment & Waste
Documentation
Data Sheets
Product Manuals
Certifications & Approvals
- Certifications & Approvals - CCS CE Certificate of Declaration pdf 225 KB
- Certifications & Approvals - CCS CRN Approval - Alberta pdf 126 KB
- Certifications & Approvals - CCS CRN Approval - BC pdf 67 KB
- Certifications & Approvals - CCS NACE Declaration 2013 pdf 114 KB
- Certifications & Approvals - CCS PED 2011 pdf 94 KB
- Certifications & Approvals - CCS RoHS/REACH 2012 pdf 278 KB
- Certifications & Approvals - NEMA 605 2012 pdf 24 KB