Approvals & Certifications
Set Point Range - Increasing °C
Set Point Range - Decreasing °C
Set Point Range - Increasing °F
Set Point Range - Decreasing °F
Deadband, Approx. at Top of Range °C
Deadband, Approx. at Bottom of Range °C
Deadband, Approx. at Top of Range °F
Deadband, Approx. at Bottom of Range °F
Process Connection Type & Size
Process Connection Material
Electrical Connection Size
Electrical Termination Type
- Wire Leads 18" (45 cm)
- Wire Leads 18" (45 cm) Teflon for Low Temp
- Wire Leads 2 m (200 cm)
- Connector with 4-Blades - SPDT. DIN-43650
Electrical Contacts Material
Voltage Electrical Rating
Electrical Termination Type
- 18" (45 cm) Free Leads
- 18" (45 cm) Teflon Leadwire
System Pressure
- bar: 86
- kPa: 8,618
- psig: 1,250
Electrical Rating
- 1 A at 125 Vac, 50/60 Hz
- 11 A at 125/250 Vac
Capillary Length
- 10 ft (3 m)
- 15 ft
- 25 ft
- 5 ft (1.524 m)
Capillary Material
- Stainless Steel, Graphite & Lubricated Glass Fiber
Electrical Enclosure Certification
- CSA Listed by Canadian Standard Association (CSA) Testing Laboratories (File LR22665) for Enclosure
Approvals & Certifications
- CE
- CRN - Canadian Registration Number
- CRN - Alberta
- CRN - British Columbia
- CRN - Manitoba
- CRN - N.W. Territories
- CRN - Saskatchewan
- CSA
- LVD
- PED
- RoHS
Maximum Sensor, Probe Temperature
- 93° to 371° C (200° to 700° F)
Electrical Connectors
- 1/2" NPT Male
- 4-Blades, Conforms to DIN-43650
Set Point Range - Increasing
- -7° to 343° C
- -7° to 343° C (20° to 650° F)
Deadband, Approximate - Top of Range
- -15° to -12° C (5° to 10° F)
- 4° to 5° C (39° to 41° F)
Set Point Range - Decreasing
- -18° to 338° C
- -18° to 338° C (0° to 640° F)
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Deadband, Approximate - Bottom of Range
- 11° to 14° C (52° to 57° F)
- -7° to -4° C (20° to 25° F)
Proof Pressure
- bar: 103.4
- kPa: 10,342
- psig: 1,500