Accuracy
- 0.1 % of Full Scale (Includes Effects of Linearity, Hysteresis & Repeatability)
Ambient Temperature Range
- -40° to 80° C (-40° to 176° F)
Current
- Excitation Current RTD: 0.8 mA
Output
- 4-20 mA Loop Powered, Linear to Temperature
Power Supply
- 12-32 Vdc, Polarity Protected
Resistance
- Sensor Lead Resistance RTD: 500 ohms, Max.
Sensor Circuit
- Open Circuit Detection (Over-Scale Limit): 27 mA
- Open Circuit Detection (Under-Scale Limit): 2.2 mA
Sensor, Probe Type
- Pt100 RTD, α=0.00385, DIN EN 60751
Span & Zero Adjustments
- ± 10 % for Zero & Span
- 20-Turn Potentiometer
Stability
- Long Term Drift: ± 0.05 % of Full Scale Per Year
Storage Temperature
- -40° to 80° C (-40° to 176° F)
Temperature Range
- Pt100: -50° to 600° C (-58° to 1,112° F)
Thermal Drift
- Span & Zero Drift: ± 0.01 % of Full Scale/°C