6900GE Series Pressure Switch
Brand: Custom Control Sensors, LLCThe hazardous locations 6900GE Series is the most popular, all-around, all-aluminum gage pressure switch.
The series is UL/CSA explosion proof, Class I, Groups A, B, C and D, and Class II Groups E, F and G certified. NEMA 4X and IP66 rating is optimum for wet conditions.
It is designed with high vibration and shock resistance utilizing Dual Snap® disc spring technology ensuring high accuracy and repeatability.
It comes with high over-pressure capabilities and still relatively compact in size to conveniently mount on panels. It meets the demand for all applications commercial, industrial and otherwise.
Features- Adjustable Set Point Range
- Increasing
- psig 3 - 3400
- kPa 20.7 - 23,442.15
- bar 0.21 - 234
- Decreasing
- psig 1 - 3180
- kPa 6.9 - 21,925.3
- bar 0.07 - 219
- Increasing
- Deadband - Approximate: 2 - 220 psi, 13.8 - 1516.8 kPa, 0.14 - 5.2 bar
- System Pressure - Maximum: 500 - 5000 psig, 3447.38 - 34,473.75 kPa, 34.5 - 345 bar
- Proof Pressure: 750 - 7500 psig, 5171.07 - 51,710.63 kPa, 51.7 - 517 bar
- Wetted Materials
- Pressure Port: 1/4"-18 Female NPT Aluminum
- Diaphragm: Polyimide
- O-Ring: Buna N
- Relay: SPDT or DPDT
- UL, CSA
- Explosion Proof - Class 1, Div/Zone 1, Groups A, B, C and D
- Dual Seal - ANSI/ISA - 12.27.01-2003
- CRN, CE Mark, NEMA
Specifications
Area Classification
- Hazardous Area
Approvals
- ATEX
- CE
- CCC
- CRN
- CSA
- cUL
- Dual Seal
- GOST
- IECEx
- UL
Adjustable or Pre-Set Set Point
- Field Adjustable
Set Point - PSI ▲
- Minimum: 3
- Maximum: 3400
Set Point - PSI ▼
- Minimum: 1
- Maximum: 3180
Set Point - kPa ▲
- Minimum: 20.68
- Maximum: 23442
Set Point - kPa ▼
- Minimum: 6.89
- Maximum: 21925
Set Point - BAR ▲
- Minimum: 0.21
- Maximum: 234
Set Point - BAR ▼
- Minimum: 0.07
- Maximum: 219
Deadband - PSI Approx.
- Minimum: 2
- Maximum: 220
Deadband - BAR - approx.
- Minimum: 0.14
- Maximum: 15.2
Process Connection Type & Size
- 1/4"-18 NPT Female
- 1/2"-14 NPT Female
- 1/2"-14 NPT Male
- 1/2"-14 NPT Female - Welded Capsule, No O-Ring
Process Connection Material
- Aluminum
- Stainless Steel
- Monel
- Hastelloy C-276
System Pressure - Max.
- 500 psig : 34.5 bar : 3447 kPa
- 5000 psig : 345 bar : 3447 kPa
Proof Pressure - Max.
- 750 psig : 51.7 bar : 5171 kPa
Diaphragm Material
- Polyimide
- Stainless Steel
- Monel
- Hastelloy C-276
NACE
- NACE MR 0175 / ISO 15156
O-Ring
- Buna-N
- Ethylene Propylene
- No O-Ring c/w Welded Capsule
Enclosure Rating
- IP 66
- NEMA 4
- NEMA 7
- NEMA 9
- NEMA 13
Operating Temp. Range °C
- Minimum: -40
- Maximum: 86
Operating Temp. Range °F
- Minimum: -40
- Maximum: 186
Reset Function - Auto or Manual
- Auto
Electrical Connection Size
- 1/2"-14 NPT Male
- M20
Electrical Termination Type
- Wire Leads 18" : 45 cm
- Wire Leads 18" : 45 cm Teflon for Low Temp
- Wire Leads 2 m : 200 cm
Electrical Contacts Form
- SPDT
- DPDT
Electrical Contacts Material
- Silver
- Gold
Voltage Electrical Rating
- 0 - 250 VAC
- 0 - 125 VDC
Ampere Rating
- 0.5 to 11 A
SIL Level
- SIL 2
- SIL 3
RoHS
Housing Material
- Aluminum
- Stainless Steel
Gender
- Male
- Female
Service
- Sweet - Oil & Gas
Electrical Rating
- 1 A at 125 Vac, 50/60 Hz
- 11 A at 125/250 Vac
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Electrical Certification
- ATEX - SIRA Certified for Potentially Explosive Atmospheres. Models 6****Y, II 2 GD Ex d IIC, 08-ATEX-
- cUL, UL/CSA, Hazardous Areas, Div. 1, 2
- IECEx - SIRA Certified, SIR 10,0193X (Option Y)
Switch Type
- SPDT
- DPDT
Approvals & Certifications
- ATEX
- CE
- CRN - Canadian Registration Number
- CRN - Alberta
- CRN - British Columbia
- CRN - Manitoba
- CRN - N.W. Territories
- CRN - Saskatchewan
- CSA
- cUL
- Dual Seal
- IEC Ex
- LVD
- PED
- RoHS
- RTN
- UL
Environmental Protection
- IP 54
- IP 66
- NEMA 4
- NEMA 7
- NEMA 9
- NEMA 13
Proof Pressure
- bar: 51.7 to 310
- kPa: 5,171 to 31,026
- psig: 750 to 4,500
O-Ring Material
- Buna-N
- Ethylene Propylene (EPR)
- Viton
- None
Diaphragm Material
- Hastelloy C-276
- Monel
- Polyimide
- Stainless Steel
Process Connection
- 1/2" NPT Female Welded Diaphragm - Internal with Port Cavity
- 1/4" NPT Female
Electrical Contacts
- Silver
- Gold
Deadband, Approximate
- bar: 0.14 to 15.2
- kPa: 13.8 to 1,517
- psi: 2 to 220
Adjustment Type
- Field Adjustable
Process Connection Material
- 316 Stainless Steel
- Aluminum
- Hastelloy C-276
- Monel
Electrical Assembly
- 316 Stainless Steel
- Hermetic Seal
Enclosure, Body Material
- Aluminum
- Stainless Steel
System Pressure
- bar: 34.5 to 207
- kPa: 3,447 to 20,684
- psig: 500 to 3,000
Set Point Range - Increasing
- bar: 0.21 to 234
- kPa: 20.7 to 23,442
- psig: 3 to 3,400
Electrical Termination Type
- 18" (45 cm) Free Leads
- 18" (45 cm) Teflon Leadwire
Electrical Connectors
- 1/2" NPT Male
- M20 Male
Set Point Range - Decreasing
- bar: 0.07 to 219
- kPa: 6.9 to 21,925
- psig: 1 to 3,180
Area Classification
- Hazardous Area
- Boilers & Burners
- Chemical & Petrochemical Plants
- Chemical Refining & Processing
- Degreasers & Evaporators
- Fluid Management
- Ground Support Equipment
- Hydraulic & Lubrication Systems
- Heating & Air Conditioning
- Manufacturing Process
- Oil & Gas
- Pipelines
- Power Generation
- Power Plants
- Pulp & Paper Mills
- Pumps, Compressors & Turbines
- Recovery Systems
- Refineries
- Reverse Osmosis Systems & Filters
- Safety Systems
- Specialized OEM Equipment
- Steel Mills
- Utilities
- Water Treatment, Waste & Sewage Treatment Facilities
Documentation
Data Sheets
Product Manuals
Certifications & Approvals
- Certifications & Approvals - CCS Approval Matrix pdf 34 KB
- Certifications & Approvals - CCS ATEX 6900, 674, 611 May 2011 pdf 153 KB
- Certifications & Approvals - CCS CE Certificate of Declaration pdf 225 KB
- Certifications & Approvals - CCS CRN Approval - Alberta pdf 126 KB
- Certifications & Approvals - CCS CRN Approval - BC pdf 67 KB
- Certifications & Approvals - CCS CRN Approval - Manitoba pdf 79 KB
- Certifications & Approvals - CCS CRN Approval - NWT pdf 87 KB
- Certifications & Approvals - CCS CRN Approval - Saskatchewan pdf 263 KB
- Certifications & Approvals - CCS CSA Certification Record - Hazardous pdf 32 KB
- Certifications & Approvals - CCS Declaration of Conformity pdf 98 KB
- Certifications & Approvals - CCS EMC Directive pdf 30 KB
- Certifications & Approvals - CCS IECEx Certificate of Conformity pdf 1.3 MB
- Certifications & Approvals - CCS LVD - Low Voltage Directive pdf 98 KB
- Certifications & Approvals - CCS PED 2011 pdf 94 KB
- Certifications & Approvals - CCS RoHS/REACH 2012 pdf 278 KB