605T Series Temperature Switch

Brand: Custom Control Sensors, LLC (CCS)

Specifications

  • Adjustable Set Point Range
    • Increasing
      • -30° to 420° F
      • -34° to 216° C
    • Decreasing
      • -39° to 414° F
      • -39° to 212° C
  • Deadband - Approximate
    • At Bottom of Range: 9° to 19° F, 5° to 11° C
    • At Top of Range: 3° to 6° F, 2° to 4° C
  • Probe Temperature - Maximum: 250° to 500° F, 121° to 260° C
  • Wetted Materials
    • Temperature Probe: 300 Stainless Steel, Nickel Plated Steel
    • O-Ring: Buna N or Silicone Rubber
  • Relay: SPDT or DPDT
  • UL, CE Mark, General Purpose

Specifications

Area Classification

  • Non-Hazardous Area

Approvals

  • CE
  • CCC

Field Adjustable or Pre-Set Set Point

  • Field Adjustable

Process Connection Type & Size

  • 1/2"-14 NPT Male

Process Connection Material

  • 300 Stainless Steel

NACE

  • NACE MR 0175 / ISO 15156

O-Ring

  • Buna-N
  • Silicone Rubber

Enclosure Rating

  • IP 66
  • NEMA 4
  • NEMA 4X
  • NEMA 13

Electrical Connection Size

  • 1/2" -14 NPT Female

Electrical Termination Type

  • Terminal Strip

Electrical Contacts Form

  • SPDT
  • DPDT
  • Double Break

Electrical Contacts Material

  • Silver
  • Gold

Voltage Electrical Rating

  • VAC 0 - 250
  • VAC 251 - 480
  • VDC 0 - 125
  • VDC 126 - 250

Ampere Rating

  • 0.2 to 15 A

RoHS Compliance

  • Yes

Housing Material

  • Aluminum

Gender

  • Female

Electrical Connectors

  • Terminal Strip - Internal

Set Point Range - Decreasing

  • 1° to 100° C (34° to 212° F)
  • 101° to 250° C (214° to 482° F)
  • -39° to 212° C (-38° to 414° F)
  • -50° to 0° C (-58° to 32° F)

Electrical Rating

  • 1 A at 125 Vac, 50/60 Hz
  • 15 A at 125/250/480 Vac Resistive, 0.4 A at 125 DC, 0.2 A at 250 DC
  • 5 A at 125/250 Vac Resistive, 5 A at 28 DC, 0.5 A at 125 DC

Deadband, Approximate - Bottom of Range

  • -13° to -7° C (9° to 19° F)
  • 5° to 12° C (41° to 54° F)

Operating Temperature

  • -40° to 86° C (-40° to 187° F)

Proof Pressure

  • bar: 103.4
  • kPa: 10,342
  • psig: 1,500

System Pressure

  • bar: 86
  • kPa: 8,618
  • psig: 1,250

Maximum Sensor, Probe Temperature

  • 121° to 260° C (250° to 500° F)

Standard Features

  • Internal Case Ground
  • Weatherproof

Deadband, Approximate - Top of Range

  • -16° to -14° C (3° to 6° F)
  • 2° to 8° C (36° to 46° F)

Sensor, Probe Material

  • Stainless Steel with Nickel-Plated Steel

Set Point Range - Increasing

  • 1° to 100° C (34° to 212° F)
  • 101° to 250° C (214° to 482° F)
  • -34° to 216° C (-30° to 420° F)
  • -50° to 0° C (-58° to 32° F)
show more