Approvals & Certifications
Set Point Range - Increasing - psi
Set Point Range - Decreasing - psi
Set Point Range - Increasing - kPa
- Minimum: 13.78
- Maximum: 517.1
Set Point Range - Decreasing- kPa
- Minimum: 4.13
- Maximum: 475.73
Set Point Range - Increasing - bar
- Minimum: 0.138
- Maximum: 5.2
Set Point Range - Decreasing - bar
- Minimum: 0.041
- Maximum: 4.76
Deadband, Approx. - bar
- Minimum: 0.096
- Maximum: 0.414
System Pressure - Max.
- 400 psig : 28 bar : 2757 kPa
Process Connection Type & Size
Process Connection Material
Enclosure Rating
- IP 66
- NEMA 4
- NEMA 4X
- NEMA 13
Electrical Connection Size
Electrical Termination Type
Electrical Contacts Material
Voltage Electrical Rating
- 0 - 250 VAC
- 251 - 480 VAC
- 0 - 125 VDC
- 126 - 250 VDC
Proof Pressure - High Over Low
- bar: 28
- kPa: 2,758
- psig: 400
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Approvals & Certifications
- CE
- CRN - Canadian Registration Number
- CRN - Alberta
- CRN - British Columbia
- CRN - Saskatchewan
- EMC
- LVD
- PED
- RoHS
Proof Pressure - Low Over High
- bar: 6.9
- kPa: 689.47
- psig: 100
Set Point Range - Increasing
- bar: 0.138 to 5.2
- kPa: 13.8 to 517.1
- psid: 2 to 75
O-Ring Material
- Ethylene Propylene (EPR)
- Viton
Electrical Rating
- 1 A at 125 Vac, 50/60 Hz
- 15 A at 125/250/480 Vac Resistive, 0.4 A at 125 Vdc, 0.2 A at 250 Vdc
- 5 A at 125/250 Vac Resistive, 5 A at 28 Vdc, 0.5 A at 125 Vdc
System Pressure
- bar: 28
- kPa: 2,758
- psig: 400
Electrical Connectors
- 1/2" NPT Female Conduit Connection
- Terminal Strip - Internal
Process Connection Material
Environmental Protection
- IP 65
- IP 66
- NEMA 4
- NEMA 4X
- NEMA 13
Set Point Range - Decreasing
- bar: 0.034 to 4.76
- kPa: 3.5 to 475.7
- psid: 0.5 to 69
Proof Pressure - Both Ports
- bar: 52
- kPa: 5,171
- psig: 750
Deadband, Approximate
- bar: 0.103 to 0.414
- kPa: 10.4 to 41.3
- psi: 1.5 to 6