646VZE Series Pressure Switch
Brand: Custom Control Sensors, LLC (CCS)Specifications
- Adjustable Set Point Range - VACUUM
- Increasing
- Inches Hg 3.5 - 28.5
- mm Hg 89 - 724
- Decreasing
- Inches Hg 1 - 26
- mm Hg 25 - 660
- Increasing
- Deadband - Approximate: 2.5 Inches Hg, 64 mm Hg
- System Pressure - Maximum: 150 psig, 1034.21 kPa, 10.3 bar
- Proof Pressure: 250 psig, 1723.69 kPa, 17.2 bar
- Wetted Materials
- Pressure Port: 1/2" Female NPT 316 Stainless Steel
- Diaphragm: Polyimide
- O-Ring: Viton
- Relay: SPDT or DPDT
- UL, CSA
- Explosion Proof - Class 1, Div/Zone 1, Groups A, B, C and D
- CRN, CE Mark, Dual Seal
Specifications
Pressure Type
- Vacuum Pressure
Area Classification
- Hazardous Area
Approvals
- ATEX
- CE
- CSA
- cUL
- Dual Seal
- GOST
- UL
Field Adjustable or Pre-Set Set Point
- Field Adjustable
Process Connection Type & Size
- 1/4"-18 NPT Female
Process Connection Material
- Stainless Steel
Proof Pressure - Max.
- 250 psig : 17.2 bar : 1723.68 kPa
Diaphragm Material
- Polyimide
- Stainless Steel
NACE
- NACE MR 0175 / ISO 15156
O-Ring
- Ethylene Propylene
- Viton
Enclosure Rating
- IP 66
- NEMA 4
- NEMA 7
- NEMA 9
- NEMA 13
Electrical Connection Size
- 1/2"-14 NPT Male
Electrical Termination Type
- Wire Leads 18" : 45 cm
- Wire Leads 18" : 45 cm Teflon for Low Temp
- Wire Leads 2 m : 200 cm
Electrical Contacts Form
- SPDT
- DPDT
- Double Break
Electrical Contacts Material
- Silver
- Gold
Voltage Electrical Rating
- VAC 0 - 250
- VAC 251 - 480
- VDC 0 - 125
- VDC 126 - 250
Ampere Rating
- 0.2 to 15 A
SIL Level
- SIL 2
- SIL 3
RoHS Compliance
- Yes
Housing Material
- Aluminum
Gender
- Female
Service
- Sweet - Oil & Gas
Deadband, Approximate
- inHg: 2.5
- mmHg: 64
System Pressure
- bar: 10.3
- kPa: 1,034
- psig: 150
Electrical Assembly
- Hermetic Seal
Proof Pressure
- bar: 17.24
- kPa: 1,724
- psig: 250
Set Point Range - Decreasing
- inHg: -1 to 26
- mmHg: -25 to 660
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Set Point Range - Increasing
- inHg: -3.5 to 28.5
- mmHg: -89 to 724
Electrical Certification
- ATEX - Baseefa Certified for Potentially Explosive Atmospheres. Models 646**Y, II 2 GD Ex d IIC, Baseefa 05-ATEX-0011X. (Option Y)
- cUL, UL/CSA, Hazardous Areas, Div. 1, 2
Electrical Rating
- 1 A at 125 Vac, 50/60 Hz
- 15 A at 125/250/480 Vac Resistive, 0.5 A at 125 Vdc, 0.2 A at 250 Vdc
- 5 A at 125/250 Vac Resistive, 5 A at 28 Vdc, 0.5 A at 125 Vdc
Electrical Connectors
- 1/2" NPT Male
Area Classification
- Hazardous Area
Documentation
Data Sheets
Product Manuals
Certifications & Approvals
- Certifications & Approvals - CCS 646 Dec 2005 pdf 96 KB
- Certifications & Approvals - CCS 646 Feb 2005 pdf 164 KB
- Certifications & Approvals - CCS 646 Jan 2007 pdf 92 KB
- Certifications & Approvals - CCS Approval Matrix pdf 34 KB
- Certifications & Approvals - CCS CE Certificate of Declaration pdf 225 KB
- Certifications & Approvals - CCS CRN Approval - Alberta pdf 126 KB
- Certifications & Approvals - CCS CRN Approval - BC pdf 67 KB
- Certifications & Approvals - CCS CRN Approval - Manitoba pdf 79 KB
- Certifications & Approvals - CCS CRN Approval - NWT pdf 87 KB
- Certifications & Approvals - CCS CRN Approval - Saskatchewan pdf 263 KB
- Certifications & Approvals - CCS CSA Certification Record - Hazardous pdf 32 KB
- Certifications & Approvals - CCS EMC Directive pdf 30 KB
- Certifications & Approvals - CCS LVD - Low Voltage Directive pdf 98 KB
- Certifications & Approvals - CCS NACE Declaration 2013 pdf 114 KB
- Certifications & Approvals - CCS PED 2011 pdf 94 KB
- Certifications & Approvals - CCS RoHS/REACH 2012 pdf 278 KB