Approvals & Certifications
Set Point Range - Increasing - psi
- Minimum: 1.45
- Maximum: 2306
Set Point Range - Decreasing - psi
- Minimum: 0.44
- Maximum: 2126
Set Point Range - Increasing - kPa
- Minimum: 9.9974
- Maximum: 15899.31
Set Point Range - Decreasing- kPa
- Minimum: 3.0337
- Maximum: 14658.25
Set Point Range - Increasing - bar
Set Point Range - Decreasing - bar
- Minimum: 0.03
- Maximum: 146.6
Deadband, Approx. - psi
- Minimum: 1.01
- Maximum: 180
Deadband, Approx. - bar
- Minimum: 0.07
- Maximum: 12.4
System Pressure - Max.
- 507 psig : 35 bar : 3495 kPa
Proof Pressure - Max.
- 754 psig : 52 bar : 5198 kPa
Process Connection Type & Size
Process Connection Material
Enclosure Rating
- IP 66
- IP 67
- NEMA 4
- NEMA 7
- NEMA 9
- NEMA 13
Reset Function - Auto or Manual
Electrical Connection Size
Electrical Termination Type
Electrical Contacts Material
Voltage Electrical Rating
- 0 - 250 VAC
- 251 - 480 VAC
- 0 - 125 VDC
- 126 - 250 VDC
Environmental Protection
- IP 66
- IP 67
- NEMA 4
- NEMA 7
- NEMA 9
- NEMA 13
Electrical Certification
- ATEX - Certificate No. Baseefa 04-ATEX-0113. Baseefa Certified for Potentially Explosive Atmospheres Electrical Assembly Series. in Compliance with EN 60079-0: 2004, EN 60079-1: 2004 & EN 50281-1-1: 1998 + Amendment 1. (Standard)
Electrical Rating
- 5 A at 28 Vdc
- 0.5 A at 125 Vdc
- 0.5 A at 125 DC
- 11 A at 125/250 Vac Resistive
- 15 A at 125/250/480 Vac Resistive
System Pressure
- bar: 35 to 207
- kPa: 3,496
- psig: 507 to 3,000
Set Point Range - Decreasing
- bar: 0.030 to 146.6
- kPa: 03.03 to 14,658
- psi: 0.44 to 2,126
Approvals & Certifications
- ATEX
- CSA
- EMC
- GOST-R
- LVD
- RoHS
- RTN
- UL
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Set Point Range - Increasing
- bar: 0.1 to 159
- kPa: 10 to 15,899
- psi: 01.45 to 2,306
Deadband, Approximate
- bar: 0.07 to 12.4
- kPa: 7.0 to 1,241
- psig: 1.01 to 180
Proof Pressure
- bar: 52 to 310
- kPa: 5,199 to 31,026
- psig: 754 to 4,500
Process Connection Material