Accuracy
- ± 0.25 % of Full Scale
- ± 0.5 % of Full Scale
Approvals & Certifications
Compensated Temperature
- 2° to 57° C (35° to 135° F)
Humidity
- 10 to 95 % Relative Humidity
Loop Resistance
- 0 to 1045 ohms Vmin=12 V+[(.22 A)(RL)]
Media
- Air
- Non-Conductive, Non-Corrosive Gases
NACE & NIST
- NIST Traceable Calibration Certificate
Process Connection Material
- Barbed Stainless Steel for 3/16” I.D. Tubing
Span & Zero Adjustments
- ± 10 % of Full Scale Adjustment
- Externally Accessible Potentiometers
- Non-Interactive
Stability
- ± 0.5 % of Full Scale Output/Year
Temperature Effect
- ± 0.015 % of Full Scale/°F (Zero & Span)
Temperature Range
- -29° to 71° C (-20° to 160° F)