Model T9000 Electro-Pneumatic Pressure Controller

Brand: Fairchild Industrial Products

The Rotork Fairchild T9000 Series Electro-Pneumatic Pressure Controller has a closed-loop, integrated, microprocessor control system that regulates outlet pressure. 
 
The Model T9000 controls pressure in proportion to an analog electrical input signal. An internal feedback sensor monitors output pressure to achieve high accuracy. 
 
You can control the output from the Model T9000 using the keypad or from an analog control signal. You can control the output from the Model T9000D using the keypad and through DeviceNet™ Communication network.
 
With its integral booster sections, the T9000 series of I/P pressure controllers delivers high accuracy at flow capacities of 1 SCFM in the T9000, 90 SCFM in the T9020, 110 SCFM in the T9040, 220 SCFM in the T9060, and 700 SCFM in the T9080.
Features
  • High Flow Capacity of up to 700 SCFM (1,190 m3/Hr)
  • Output pressure displays in psig, BAR, kPa, or user-defined pressure units
  • Reverse acting capability for analog input and output signals
  • Select Current or Voltage mode for input signal
  • Independently adjustable PID tuning coefficients
  • Fully functional keypad and display
  • Backlit Liquid Crystal display screen

Specifications

Accuracy

  • < 0.50 % Output Span

Air Consumption

  • 0 at Steady State Output with Deadband at 1 % of Full Scale

Approvals & Certifications

  • EMC 89/336/EEC, EMC Directive

BSP Connection

  • 1” BSPP Female
  • 1” BSPT Female
  • 1/2” BSPP Female
  • 1/2” BSPT Female
  • 1/4” BSPP Female
  • 1/4” BSPT Female
  • 3/4” BSPP Female
  • 3/4” BSPT Female
  • 3/8” BSPP Female
  • 3/8” BSPT Female

Deadband

  • Adjustable from 0 to 10 % of Full Scale

Elastomers

  • Fluorocarbon
  • Nitrile

Enclosure Finish

  • Epoxy Coated

Enclosure, Body Material

  • Chromate Treated Aluminum
  • Polymer

Exhaust Capacity - Relieving Units Only

  • 1 to 350 scfm where Downstream Pressure is psig: 60 (kPa: 400, bar: 4)

Exhaust Port

  • Tapped Exhaust Port

Flow Rate

  • 1 to 700 scfm at psig: 150 (kPa: 1,034, bar: 10) Supply

Frequency

  • -3 dB at 1 Hz Per ISA S26.4.3.1 Load Configuration A

Input

  • 0-10 Vdc / 400 ohms Min.
  • 4-20 mA / 500 ohms, Max.
  • DeviceNet

Input Power

  • Power Consumption: < 5 Watts

NPT Connection

  • 1” NPT Female
  • 1/2” NPT Female
  • 1/4” NPT Female
  • 3/4” NPT Female
  • 3/8” NPT Female

Output

  • Analog Output Signal / Impedence: 0-10 Vdc / 400 ohms Min.
  • Analog Output Signal / Impedence: 4-20 mA / 500 ohms, Max.

Pressure Range

  • bar: 0 to 10
  • kPa: 0 to 1,000
  • psig: 0 to 150

Pressure Type

  • Gauge

RFI/EMI Effect

  • < 0.5 % EMC Directive 89/336/EEC European Norms EN 50081-2 & EN 50082-2

Supply Pressure - Maximum

  • psig: 200 (kPa: 1,400, bar: 14)

Supply Voltage

  • 24 Vdc ± 10 %

Temperature Range

  • -18° to 71° C (0° to 160° F)

Trim Material

  • Zinc-Plated Steel

Vibration Effect

  • < 1 % of Span Under the Following Conditions: 5 to 15 Hz at 0.8” Constant Displacement 15 to 500 Hz at 10 G's
show more